Intelligent Series

SFC-500 Series
Intelligent Fire Alarm Control Panels

The SFC-500 Series Fire Alarm Control Panels are single loop addressable panels with support for up to 60, 126 or 378 addressable points. The SFC-500 Series panels are equipped with a two line by 20 character back-lit LCD display, numerical keypad and an integrated UDACT/Digital Communicator.  The SFC-500 Series family also includes remote LED and LCD annunciators.

The SFC-500 Series panels are ideal for both new and  retrofit applications.  Designed for small to medium commercial, institutional and industrial occupancies, these panels are powerful enough to meet today's installation demands.  The SFC-500 Series panels are configurable by the keypad for onsite programming or by a PC for both onsite and remote programming.  Easy to install and simple to operate and configure, the SFC-500 Series panels enable the installer to configure the system to meet their specific requirements.

> Catalog


SFC-100 Panels

SFC-102R
FACP Micropr. based, 2 Style B/Y, 4.2 Amp, Ann.SRAM-105, Red

  • The SFC-102 is equipped with two Style B (Class B) initiating circuits, two Style Y (Class B) notification appliance circuits, one Form "C" common alarm relay, one Form "C" common trouble relay, one non-switched Aux. Power output and one switched Aux. Power output.

  • The panel also has individual alarm, supervisory and trouble LED indicators per zone.

  • The panel features a 6.0A power supply, which provides a full 3.0A of NAC power, 0.5A Aux. power with the balance to run the panel and charge the batteries.

  • No extra transformers or added power supplies are required.

  • In addition the panels has 500mA of Auxiliary power with switched and un-switched outputs.



SFC-105R
FACP Micropr.based, 5 Style B Init.Zones, 2 Style Y Ccts, 4.2Amp, Red

  • The SFC-105 is equipped with five Style B (Class B) initiating circuits, two Style Y (Class B) notification appliance circuits, one Form "C" common alarm relay, one Form "C" common trouble relay, one non-switched Aux. Power output and one switched Aux. Power output.

  • The panel also has individual alarm, supervisory and trouble LED indicators per zone.

  • The panels feature a 6.0A power supply, which provides a full 3.0A of NAC power, 0.5A Aux. power with the balance to run the panel and charge the batteries.

  • No extra transformers or added power supplies are required.

  • In addition the panels has 500mA of Auxiliary power with switched and un-switched outputs.



SFC-200 Panels

SFC-200-6DDR
6 Zone Fire Alarm Panel c/w LCD Display & UDACT, Red Finish

  • The SFC-200-6DR and SFC-200-6DDR are equipped with six Class "B" (Style "B") initiating circuits and two Class "B" (Style "Y") indicating circuits rated @ 1.7 Amps maximum. (Total of 5 Amps)  

  • The SFC-200-6DDR is equipped with a built-in UDACT/Digital Communicator.  

  • One SICA-206 Six Initiating Circuit Class "A" Converter Modules may be used for Class "A" (Style "D") wiring of the initiating circuits.

  • One SOCA-202 Two Indicating Circuit Class "A" Converter Module may be used for Class "A" (Style "Z") wiring of the indicating circuits.  

  • The cabinet will support up to 12 AH batteries.

  • The panels can be semi-flush mounted with the optional SFC-200TRB trim ring. Note: Not ULC listed.




SFC-200-6LDR
6 Zone FAP w/ Alarm & Trouble LEDs & UDACT, Red

  • The SFC-200-6DR and SFC-200-6DDR are equipped with six Class "B" (Style "B") initiating circuits and two Class "B" (Style "Y") indicating circuits rated @ 1.7 Amps maximum. (Total of 5 Amps)

  • The SFC-200-6DDR is equipped with a built-in UDACT/Digital Communicator.

  • One SICA-206 Six Initiating Circuit Class "A" Converter Modules may be used for Class "A" (Style "D") wiring of the initiating circuits.

  • One SOCA-202 Two Indicating Circuit Class "A" Converter Module may be used for Class "A" (Style "Z") wiring of the indicating circuits.

  • The cabinet will support up to 12 AH batteries.

  • The panels can be semi-flush mounted with the optional SFC-200TRB trim ring.



SFC-201-12DDR
12 Zone Fire Alarm Panel c/w LCD Display & Udact, Red

  • The SFC-201-12DDR is equipped with twelve Class "B" (Style "B") initiating circuits and four Class "B" (Style "Y") indicating circuits @ 1.7 Amps maximum. (Total of 5 Amps).

  • One SICA-206 Six Initiating Circuit Class A Converter Module may be used for Class "A" (Style "D") wiring of the initiating circuits.

  • One SOCA-204 Four Indicating Circuit Class "A" Converter Module may be used for Class "A" (Style "Z") wiring of the Indicating circuits.  

  • The SFC-201-12DDR has a built-in UDACT/Digital Communicator and the cabinet will support up to 12 AH batteries.

  • The panel can be semi-flush mounted with the optional SFC-UNIV-TRB trim ring.



SFC-201-12LDR
12 Zone Fire Alarm Panel c/w LED Display & Udact, Red

  • The SFC-201-12LDR is equipped with twelve Class "B" (Style "B") initiating circuits and four Class "B" (Style "Y") indicating circuits rated @ 1.7 Amps maximum. (Total of 5 Amps)  

  • Two SICA-206 Six Initiating Circuit Class "A" Converter Modules may be used for Class "A" (Style "D") wiring of the initiating circuits.

  • One SOCA-204 Four Indicating Circuit Class "A" Converter Module may be used for Class "A" (Style "Z") wiring of the indicating circuits.  

  • The SFC-201-8LDR is configurable by the keypad (using the CFG-300 Configuration Tool) for onsite programming or by a PC for both onsite and remote programming.

  • The SFC-201-12LDR has a built-in UDACT/Digital Communicator and the cabinet will support up to 12 AH batteries.

  • The panel can be semi-flush mounted with the optional SFC-UNIV-TRB trim ring.



SFC-300 Panels

SFC-308K
Series 300 8 Zone Starter Kit US. Red

  • The SFC-300 Series panels come complete with Eight Class B (Style B) Initiating Circuits which may be configured as Four Class A (Style D) Circuits.

  • The panels can be expanded up to 24 Class B or 12 Class A circuits with the addition of the SDM-308 Initiating Circuit Module.

  • In addition the panels come equipped with Four Class A/B (Style Z/Y) Indicating circuits, which are each rated at 1.7 Amps.

  • The SFC-300 Series also include a 6 Amp Power Supply which powers the system and supplies two 4-wire reset-able regulated smoke power supply of 24 VDC 200mA maximum each.

  • The SFC-300 Series panels also allow for the addition of two SSM-304 Signal Modules or two SRM-308 Relay modules in place of the SDM-308 Initiating Circuit Adder Modules.

  • (Maximum of 3 Adder modules)



 